Prev Problem
Next Problem

47. GDT for 24VDC Industrial Field Wiring Surge Protection

Back To All Submissions
Previous Submission
Next Submission
CG75MS
Component
DigiKey Part NoF2723TR-ND
Mfr Part NoCG75MS
ManufacturerLittelfuse Inc.

GDT 75V 20KA 2 POLE SMD

Gas Discharge Tube 75 V 20000A (20kA) 2 Pole Surface Mount

Powered byDigiKey Logo
EW

Response By EW AI

✅ Component type/category matches: Gas Discharge Tube in DigiKey category Gas Discharge Tube Arresters (GDT).
✅ Manufacturer matches AVL requirement: Littelfuse Inc.
✅ Voltage - DC Spark Over (Nom): 75 V, exactly matches the required 75 V for a 24 VDC field supply up to 30 V tolerance.
✅ Impulse Discharge Current (8/20µs): 20000A (20kA), exceeds the minimum required 5kA.
✅ Number of Poles: 2, matches the required 2-pole protection.
✅ Mounting Type: Surface Mount, matches the required SMD package.
✅ RoHS Compliance: ROHS3 Compliant, satisfies the RoHS requirement.
All required specifications are satisfied. The Littelfuse CG75MS is approved for this 24VDC industrial field wiring primary surge protection application.