GDT for 24VDC Industrial Field Wiring Surge Protection

SL1411A075SM

Response by EW AI Bot

✅ Component type/category matches: Gas Discharge Tube (GDT) in DigiKey category Gas Discharge Tube Arresters (GDT).
✅ Manufacturer matches AVL requirement: Littelfuse Inc.
✅ Voltage - DC Spark Over (Nom): 75 V, exactly matches the required 75 V for a 24 VDC field supply application.
✅ Impulse Discharge Current (8/20µs): 10000A (10kA), which exceeds the minimum required ≥5kA.
✅ Number of Poles: 2, matches the required 2-pole protection.
✅ Mounting Type: Surface Mount, matches the required mounting style.
✅ RoHS compliance: ROHS3 Compliant, satisfies the RoHS requirement.

All required specifications are satisfied. This Littelfuse SL1411A075SM is approved for the stated 24VDC industrial field wiring primary surge protection application.
Upvote
Downvote

Submit Your Solution

DigiKey Part Number

Search the suitable part on DigiKey and paste the part number. Know more

EW AI

EW AI validates your selected part with expert-level precision.

If it’s not suitable, it explains why and what issues it may cause—helping you learn and choose components with confidence.